Measurement and Analysis of Electromagnetic Disturbances in 500kV DC Converter Station

机译:500kV直流换流站电磁干扰的测量与分析

获取原文
获取原文并翻译 | 示例

摘要

This paper analyzes the major electromagnetic disturbance sources and their characteristics in high voltage converter station,and measures the electromagnetic disturbance in Heihe 500kV DC converter station.The measurement results shows that opening and closing process of converter valve will produce a continuous broadband electromagnetic disturbance which is much more serious in the range of MHz and declines with frequency rising.The electromagnetic disturbances above 20MHz are all fixed frequencies.And electromagnetic disturbances of high frequency are mainly for mobile phone communication signals and WIFI signals.
机译:本文分析了高压换流站的主要电磁干扰源及其特点,并对黑河500kV直流换流站的电磁干扰进行了测量。测量结果表明,换流阀的启闭过程会产生连续的宽带电磁扰动。在MHz范围内更为严重,并随频率上升而下降.20MHz以上的电磁干扰都是固定频率,而高频电磁干扰主要用于手机通信信号和WIFI信号。