Based on the theory of the zero-sequence current phase's fault location method, this article proposes a location algorithm by comparing the relationship between the time and phase radian. The implementation of this method is to use GPS(Global Positioning System) second pulse for synchronous sampling by extracting zero-sequence current, then transmit the collected phase information by the wireless communication module, and confirm the fault interval by the central station software ultimately. Considering the distribution network's branch line may result in wrong fault location, we put forward the corresponding solution. Finally, I make the analogue simulation aimed at variety of situations of distribution network's single-phase ground fault by using the simulation module of MATLAB. And I verify the fault location method is feasible by observing phase waveforms of the zero-sequence current in every outgoing line.
机译:基于零序电流相故障定位方法的理论,通过比较时间与相位弧度之间的关系,提出了一种定位算法。该方法的实现是通过提取零序电流,利用GPS(全球定位系统)第二脉冲进行同步采样,然后通过无线通信模块传输采集的相位信息,并最终由中心站软件确定故障间隔。考虑到配网的支线可能会导致错误的故障定位,我们提出了相应的解决方案。最后,利用MATLAB的仿真模块,针对配电网单相接地故障的各种情况进行了模拟仿真。通过观察每条出线零序电流的相位波形,验证了故障定位方法的可行性。