首页> 外文会议>2012 IEEE Power Electronics and Machines in Wind Applications. >Assessment of DFIG simplified model parameters using field test data
【24h】

Assessment of DFIG simplified model parameters using field test data

机译:使用现场测试数据评估DFIG简化模型参数

获取原文
获取原文并翻译 | 示例

摘要

This paper reviews and describes a simplified model of a Doubly Fed Induction Generator (DFIG) based on the IEC 61400-27 devoted to ”Electrical simulation models for wind power generation”. This Standard is focused on defining generic simulation models for both wind turbines (Part 1) and wind farms (Part 2). A brief summary regarding the current status of requirements and models is discussed in the paper. Additionally, parting from real field-test measurements of an operational wind turbine, parameters from Type 3 generic model IEC 61400-27 are fitted to the machine. The selected wind generator is located in a Spanish wind farm, in one of the regions with higher installed wind capacity. Electrical variables used to fit the model are shown and discussed based on previous works as well.
机译:本文回顾并描述了基于IEC 61400-27的双馈感应发电机(DFIG)的简化模型,该模型专用于“风力发电的电气仿真模型”。该标准的重点是为风力涡轮机(第1部分)和风电场(第2部分)定义通用仿真模型。本文讨论了有关需求和模型的当前状态的简短摘要。此外,除了对运行中的风力涡轮机进行的实际测试之外,还将类型3通用模型IEC 61400-27的参数安装到了机器上。选定的风力发电机位于西班牙风力发电场中,该风力发电场是装机容量较高的地区之一。展示和讨论了用于拟合模型的电气变量,并基于之前的工作进行了讨论。