首页> 外文会议>2012 IEEE International Power Modulator and High Voltage Conference >Real-time insulation status assessment based on standard deviation for underground cable joints
【24h】

Real-time insulation status assessment based on standard deviation for underground cable joints

机译:基于标准偏差的地下电缆接头实时绝缘状态评估

获取原文
获取原文并翻译 | 示例

摘要

The purpose of this paper is to analyze the relationship between the partial discharge and insulation status of underground cable joint. The insulation diagnosis mechanism is established by the characteristics of the probability distribution of discharge parameters. The data process of partial discharge consists of filtering and reduction, parameter extraction and parameter estimation of probability model. Four probability models were utilized, such as, Normal distribution, Log-Normal distribution, Weibull distribution and Gamma distribution. The failure of the goodness-of-fit test accompanied with huge variation of discharge parameters and striking distribution parameters. These outliers might imply that a structural variation might happen and could be used to analyze the insulation mechanism. Finally, the Normal distribution parameter for the weight of discharge region is chosen to be a feature. The threshold of insulation status is the upper limit of confidence level calculated by three standard deviations. The result shows that the outliers appeared at two sites which divide deterioration of the insulation into tree partitions, such as initial term, midterm, and final term.
机译:本文的目的是分析地下电缆接头局部放电与绝缘状态之间的关系。通过放电参数的概率分布特征建立绝缘诊断机制。局部放电的数据处理包括过滤和约简,参数提取和概率模型的参数估计。利用了四个概率模型,例如正态分布,对数正态分布,威布尔分布和伽玛分布。拟合优度测试的失败伴随着排放参数和引人注目的分布参数的巨大变化。这些异常值可能暗示可能会发生结构变化,并可以用来分析绝缘机理。最后,选择放电区域重量的正态分布参数作为特征。绝缘状态的阈值是通过三个标准偏差计算出的置信度上限。结果表明,离群值出现在两个位置,将绝缘的恶化分为树木分区,例如初期,中期和期末。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号