首页> 外文会议>2012 IEEE 34th International Telecommunications Energy Conference. >Capacity of capacitor installed in PDCs for voltage variation suppression during short circuits in HVDC power feeding systems
【24h】

Capacity of capacitor installed in PDCs for voltage variation suppression during short circuits in HVDC power feeding systems

机译:安装在PDC中的电容器的容量,用于抑制HVDC供电系统中的短路期间的电压变化

获取原文
获取原文并翻译 | 示例

摘要

This paper describes a molded-cased circuit breaker (MCCB) for higher voltage direct current (HVDC) power feeding systems. To protect circuits from fault current, such as an overcurrent or a short circuit current, an overcurrent circuit breaker is installed in power feeding systems. When a large-scale overcurrent circuit breaker is required, the case which uses MCCBs in HVDC power feeding system can be considered. However, the interrupting time of MCCBs is generally longer than that of semiconductors and fuses. Therefore, a short circuit current continues flowing for about several milliseconds until it is intercepted, and the voltage of the power feeding system continues to drop. This results in a large voltage variation of the power feeding system after a short circuit occurs when using MCCBs. We evaluated the degree of the power feeding system voltage after a short circuit occurs when using a commercial MCCB as an overcurrent circuit breaker in an HVDC power feeding system. We confirmed through experiments that the capacity of capacitor was the main factor in the voltage variation during a short circuit. We clarified the key factors concerning of the configuration of the cable condition and power distribution cabinet (PDC) for the voltage suppression when a short circuit occurs in HVDC power feeding systems equipped with MCCBs.
机译:本文介绍了一种用于高压直流(HVDC)供电系统的塑壳断路器(MCCB)。为了保护电路免受故障电流(例如过电流或短路电流)的影响,在供电系统中安装了过电流断路器。当需要使用大型过电流断路器时,可以考虑在HVDC供电系统中使用MCCB的情况。但是,MCCB的中断时间通常比半导体和保险丝的中断时间更长。因此,短路电流持续流动约几毫秒,直到被截断为止,并且供电系统的电压继续下降。使用MCCB时,在发生短路后,这会导致供电系统的电压变化很大。我们评估了在将商用MCCB用作HVDC供电系统中的过流断路器时发生短路后的供电系统电压的程度。我们通过实验证实,电容器的容量是短路期间电压变化的主要因素。我们阐明了在配备MCCB的HVDC供电系统中发生短路时,用于抑制电压的电缆状况和配电柜(PDC)配置的关键因素。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号