首页> 外文会议>2012 47th International Universities Power Engineering Conference. >Minimum voltage rating of sheath voltage limiters in underground cable systems: The influence of corrugated cable sheaths
【24h】

Minimum voltage rating of sheath voltage limiters in underground cable systems: The influence of corrugated cable sheaths

机译:地下电缆系统中护套电压限制器的最小额定电压:波纹电缆护套的影响

获取原文
获取原文并翻译 | 示例

摘要

Sheath voltage limiters (SVL) are a critical component of an underground cable's protection system. SVLs must be sized such that, under steady state fault conditions, no conduction through the arrester occurs. This could otherwise lead to a catastrophic failure. A SVL failure [1] under steady state fault conditions prompted an investigation into the adequacy of traditional approaches used to model cable sheaths and underground cable networks. Injection tests have demonstrated that the type of sheath used has a large influence over the sheath voltage profile under faulted conditions. This is particularly evident with corrugated sheaths. In this paper, two common types of corrugated sheaths are investigated — the helically corrugated sheath (HCS) and the annularly corrugated sheath (ACS). The paper establishes improved models for each type of sheath and compares these models to sheath voltage profiles obtained from injection tests on three different types of underground cable systems.
机译:护套电压限制器(SVL)是地下电缆保护系统的重要组成部分。 SVL的尺寸必须确保在稳态故障条件下不会通过避雷器导通。否则,这可能会导致灾难性的失败。在稳态故障条件下的SVL故障[1]促使人们对用于建模电缆护套和地下电缆网络的传统方法的适用性进行了研究。注入测试表明,在故障条件下,所用护套的类型对护套电压曲线有很大影响。对于波纹护套这尤其明显。在本文中,研究了两种常见的瓦楞纸护套-螺旋瓦楞纸护套(HCS)和环形瓦楞纸护套(ACS)。本文针对每种类型的护套建立了改进的模型,并将这些模型与通过三种不同类型的地下电缆系统的注入测试获得的护套电压曲线进行了比较。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号