首页> 外文会议>2012 1st International Conference on Power and Energy in NERIST. >A state-of-the-art PMU based monitoring system with Intelligent Electronic Device using microcontroller
【24h】

A state-of-the-art PMU based monitoring system with Intelligent Electronic Device using microcontroller

机译:使用微控制器的带有智能电子设备的基于PMU的最新监控系统

获取原文
获取原文并翻译 | 示例

摘要

The main objective of this paper is to monitor the phasors of voltages and currents at the sending and receiving ends of a transmission line using a microcontroller based Phasor Measurement Unit (PMU). The PMU is designed and developed to acquire the samples of voltage and current signals of the line ends in a synchronized time reference frame. The voltage and current samples from the PMUs are collected and stored in a PC using a microcontroller based Intelligent Electronic Device (IED). A MATLAB based front end graphical user interface (GUI) is developed to acquire these data using the PC's serial port. The IED coordinates all the time synchronization pulses to the PMUs and maintains a sequential routing for the data collection from them. The overall functioning of the PMUs, IED and the GUI is tested in a laboratory model of the power system and satisfactory performance is obtained.
机译:本文的主要目的是使用基于微控制器的相量测量单元(PMU)监视传输线发送和接收端的电压和电流相量。设计并开发了PMU,以在同步的时间参考帧中获取线路端的电压和电流信号样本。使用基于微控制器的智能电子设备(IED)收集来自PMU的电压和电流样本并将其存储在PC中。开发了基于MATLAB的前端图形用户界面(GUI),以使用PC的串行端口获取这些数据。 IED将所有时间同步脉冲协调到PMU,并为从它们收集的数据保持顺序的路由。在电源系统的实验室模型中测试了PMU,IED和GUI的整体功能,并获得了令人满意的性能。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号