首页> 外文会议>2010 Rural Electric Power Conference >Transformer and bus protection misoperations and how to avoid them
【24h】

Transformer and bus protection misoperations and how to avoid them

机译:变压器和母线保护误操作以及如何避免误操作

获取原文
获取原文并翻译 | 示例

摘要

The first section of the paper analyzes a transformer differential misoperation that dropped a paralleled pair of large distribution transformers serving a sizeable block of contiguous load on the eastern seaboard. This section presents the unfiltered currents measured by the numerical transformer protection relay during the unwanted operation. The misoperation occurred when the faulted distribution feeder CT saturated due to the high magnitude fault current. A recommendation is made how to prevent these types of misoperations. The second section of the paper analyzes two outages that occurred at another distribution substation in less than one month due to the misoperation of the fast bus trip scheme and a defect in the numerical overcurrent relay protecting one of the 23 kV feeders. The paper outlines the modification of the fast bus trip scheme logic to prevent this type of outage from re-occurring.
机译:本文的第一部分分析了一个变压器差动误操作,该误动使一对并联的大型配电变压器掉落,在东部沿海地区为大量的连续负载提供服务。本节介绍了数字变压器保护继电器在无用运行期间测得的未滤波电流。当故障配电馈线CT由于高强度故障电流而饱和时发生误操作。建议如何防止这些类型的误操作。本文的第二部分分析了由于快速母线跳闸方案的误操作以及保护23 kV馈线之一的数字式过电流继电器的缺陷而在不到一个月的时间里在另一个配电变电站发生的两次断电。本文概述了快速总线跳闸方案逻辑的修改,以防止此类中断再次发生。