首页> 外文会议>2010 IEEE Industrial and Commercial Power Systems Technical Conference : Conference Record >Investigation of circulating ground currents occurring during UPS/generator paralleling
【24h】

Investigation of circulating ground currents occurring during UPS/generator paralleling

机译:调查UPS /发电机并联过程中发生的循环接地电流

获取原文
获取原文并翻译 | 示例

摘要

The paralleling of uninterruptible power supplies (UPS's) with generators during UPS bypass operations can result in high-magnitude circulating ground currents under certain conditions. This paper explores the phenomena that cause this system behavior, presents data from an actual documented occurrence, and discusses methods to reduce or eliminate such circulating currents.
机译:在UPS旁路运行期间,不间断电源(UPS)与发电机的并联会导致在某些情况下产生大幅度的循环接地电流。本文探讨了导致该系统行为的现象,从实际记录的事件中提供了数据,并讨论了减少或消除此类循环电流的方法。