On the use of voltage stability index to prevent undesirable distance relay operation during voltage instability

机译:关于使用电压稳定指数防止电压不稳定期间不希望的距离继电器运行

获取原文
获取原文并翻译 | 示例

摘要

Distance relays may operate undesirably not because of faults but because of overloads and its operations have contributed to voltage collapses worldwide. To overcome this problem, the voltage stability index (VSI) is used as a criteria to differentiate between faults and voltage collapse. The VSI is developed based on the change of apparent power and it uses some local information such as bus voltage magnitude and load current magnitude. To evaluate the effectiveness of the VSI, fault and the proximity voltage collapse simulations were carried out on the IEEE 9 bus system. Results proved that the VSI is better than the SSI in terms of differentiating between a fault and a voltage instability condition. Therefore, the VSI can be applied in adaptive distance protection relaying for discriminating between a fault and a voltage collapse so as to prevent undesirable zone 3 distance relay operations.
机译:距离继电器的运行可能不是由于故障,而是由于过载,并且其操作已导致全世界范围内的电压崩溃,这是不希望的。为了克服此问题,将电压稳定指数(VSI)用作区分故障和电压崩溃的标准。 VSI是根据视在功率的变化开发的,它使用一些本地信息,例如总线电压幅度和负载电流幅度。为了评估VSI的有效性,在IEEE 9总线系统上进行了故障和接近电压崩溃仿真。结果证明,在区分故障和电压不稳定条件方面,VSI优于SSI。因此,VSI可以应用于自适应距离保护继电器中,以区分故障和电压崩溃,从而防止不希望的3区距离继电器操作。