This paper presents the effects of installing variable current-limit reactors (CLRs) and adjusting load tap changers (LTCs) on performance of a commercial wind farm in Taiwan using computer simulations. The companion paper in Part I demonstrates the field measured results, simulation model, and simulation results of the studied Jang-Bin wind farm with twenty-three 2-MW DFIG-type wind turbine generators connected to the utility system through a 23/161-kV 60-MVA step-up main transformer from six feeders. Six CLRs, that were originally designed to limit short-circuit currents under faulted conditions, are connected in series with the six feeders. The LTCs of the main transformer are used to adjust/regulate the secondary-side voltage at the 23-kV bus. Some simulated steady-state and transient results of the studied wind farm with variable values of the proposed CLRs and LTCs are analyzed and compared.
机译:本文介绍了使用计算机模拟安装可变限流电抗器(CLR)和调整负载分接开关(LTC)对台湾某商业风电场性能的影响。第一部分的随行论文展示了已研究的长滨风力发电场的现场测量结果,仿真模型和仿真结果,其中二十三台2兆瓦的DFIG型风力发电机通过23 / 161-连接到公用事业系统六个馈线的kV 60-MVA升压主变压器。六个CLR与六个馈线串联连接,这些CLR最初旨在限制故障条件下的短路电流。主变压器的LTC用于调整/调节23 kV总线上的次级侧电压。分析并比较了所研究风电场的一些模拟稳态和暂态结果,这些风电场具有建议的CLR和LTC的可变值。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号