This paper presents steady-state performance analysis of a commercial wind farm in Taiwan through field measurement results and computer simulations. The companion paper in Part II discusses the employment of current-limit reactors and load tap changers on power-quality improvement of the studied wind farm. With twenty-three 2-MW DFIG-type wind turbine generators, this wind farm is connected to the 161-kV extra high-voltage substation of Taiwan Power System through a 23/161-kV, 60-MVA step-up main transformer from six feeders. Through comparing field measured results, this paper establishes a simulation model to simulate and analyze the steady-state characteristics of the studied wind farm under disturbance conditions.
机译:本文通过现场测量结果和计算机模拟,对台湾某商业风电场的稳态性能进行了分析。第二部分的配套文件讨论了使用限流电抗器和有载分接开关来改善所研究风电场的电能质量。该风电场通过安装23台2兆瓦双馈双馈风力发电机,通过23/161 kV,60 MVA升压主变压器与台湾电力系统的161 kV超高压变电站相连。六个支线。通过比较现场测量结果,建立了一个仿真模型,以仿真和分析受扰条件下所研究风电场的稳态特性。