NEXT-GENERATION GAS DRIVEN AIR CONDITIONING SYSTEM UNDER THE CONDITION OF THE HIGHER SETTING TEMPERATURE OF THE ROOM IN THE COOLING MODE AND HIGHER VENTILATION

机译:在冷却模式和通风较高的情况下,机房的设定温度较高的情况下,新一代气体驱动空调系统

获取原文
获取原文并翻译 | 示例

摘要

In this paper, new air conditioning system in which only one desiccant rotor is connected to the vapor compression type refrigerator that is driven by the gas engine is suggested. And the performance of this system is evaluated by the simulation. The feasibility of this suggested system is as follows. (1) This system is so simple one that is a composed of the vapor compression type refrigerator and only one desiccant rotor. (2) The vapor compression type refrigerator only cools the sensible heat and needs not dehumidifying the air so that COP is enhanced greatly by increasing the evaporating temperature. (3) Two-stage regeneration is carried out. From this, the regeneration temperature of the desiccant rotor can be decreased greatly. As a result, the regeneration temperature of the desiccant rotor is only about 40℃ at the condition of the room air temperature 28℃. And COP of this system is about 20% higher than that of the conventional compression type refrigerator.
机译:在本文中,提出了一种新的空调系统,其中只有一个干燥剂转子连接到由燃气发动机驱动的蒸汽压缩式制冷机上。并通过仿真评估了该系统的性能。该建议系统的可行性如下。 (1)该系统非常简单,由蒸气压缩式制冷机和一个除湿转子组成。 (2)蒸气压缩式制冷机仅冷却显热而无需对空气进行除湿,因此通过提高蒸发温度而大大提高了COP。 (3)进行两阶段再生。由此,可以大大降低干燥剂转子的再生温度。结果,在室温为28℃的条件下,干燥剂转子的再生温度仅为40℃左右。并且该系统的COP比常规压缩式制冷机的COP高约20%。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号