A comprehensive comparison between three practical topologies of the load-balancing transformers

机译:负载平衡变压器的三种实用拓扑的全面比较

获取原文
获取原文并翻译 | 示例

摘要

Load-balancing transformer is a three-phase transformer which has a pair of additional coupling winding in the secondary-side of each phase. One of the coupling windings from each phase is in series with that of the other phase and the set of these two windings is reversely paralleled with the secondary winding of the third phase. Under unbalanced condition, the unbalanced current flows through the coupling and secondary windings that each winding is fed from primary by using a separate phase. In this way, part of excess current of one phase is transferred to the other phases. In this paper based on the original load-balancing transformer, two new load-balancing transformers are presented. Two proposed and original load-balancing transformers are simulated with MATLAB and the results are discussed.
机译:负载平衡变压器是三相变压器,在每相的次级侧都有一对额外的耦合绕组。每个相的一个耦合绕组与另一相的耦合绕组串联,并且这两个绕组的集合与第三相的次级绕组反向并联。在不平衡条件下,不平衡电流流经耦合绕组和次级绕组,每个绕组通过使用单独的相位从初级绕组馈电。这样,一相的过量电流的一部分被转移到另一相。本文基于原始的负载平衡变压器,提出了两种新型的负载平衡变压器。用MATLAB模拟了两个建议的和原始的负载平衡变压器,并对结果进行了讨论。