Experimental Study on Heat Transfer and Resistance Performance of Elliptical Finned Tube Heat Exchanger with Different Air Entrance Angles

机译:不同进气角度的椭圆翅片管换热器传热及阻力性能的实验研究

获取原文
获取原文并翻译 | 示例

摘要

To save space, sometimes the heat exchanger is necessary to arranged obliquely. Inrnview of the fact that the air entrance flow direction is not orthogonal to the heatrnexchanger surface in many cases for the direct and in-direct air cooling system, thernpresent study describes the experimental system about the elliptical finned tube heatrnexchangers inclined towards the air oncoming flow. The inclined angles between thernminor axis of the oval tube and the oncoming air flow are 90° and 60° separately. Thernheat transfer and pressure drop characteristics are investigated. The results show that thernoverall heat transfer coefficient of 60° is about 9.96 % smaller than that of 90° when thernother conditions are the same, while the pressure drop has a significant change when thernair velocity is big to some extent. At last the correlations of the convection heat transferrncoefficient and resistant coefficient of the air side are acquired. And some conclusionsrnare drawn upon the effects of the air entrance angles on the heat transfer and resistancernperformance of the elliptical finned tube heat exchanger.
机译:为了节省空间,有时需要倾斜布置热交换器。考虑到直接和间接空气冷却系统在许多情况下进气流的方向不正交于换热器表面的事实,当前的研究描述了一个椭圆形翅片管换热器朝向进气流倾斜的实验系统。椭圆管的副轴与迎面而来的气流之间的倾斜角分别为90°和60°。研究了热传递和压降特性。结果表明,在其他条件相同的情况下,总的传热系数为60°,比在90°时减小了9.96%;而当空气流速较大时,压降有较大的变化。最后得到对流换热系数与空气侧阻力系数的相关性。并针对空气进入角对椭圆形翅片管换热器的传热和阻力性能的影响得出了一些结论。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号