This paper focuses on the protection challenges associated with multi-terminal high voltage direct current (HVDC) offshore transmission networks. The applicability of fibre optic communications based differential protection to such networks is explored using a dynamic model of a five-terminal North Sea “supergrid”. Short circuit fault transients are simulated and used to define the protection requirements associated with the network. The applicability of a differential protection system using communications is investigated using the model and the operating time of the protection system is analysed with respect to the simulated fault transient behaviour, demonstrating that fault detection, discrimination and timely clearance using communication based differential protection is unlikely to be applicable to future offshore HVDC networks employing two-level Voltage Source Converters (VSCs).
机译:本文重点关注与多端子高压直流(HVDC)离岸输电网络相关的保护挑战。使用五端北海“超级电网”的动态模型探索了基于光纤通信的差动保护在此类网络中的适用性。模拟短路故障瞬态,并将其用于定义与网络相关的保护要求。使用该模型研究了使用通信的差动保护系统的适用性,并针对模拟的故障瞬态行为分析了保护系统的运行时间,表明使用基于通信的差动保护进行故障检测,识别和及时清除的可能性不大。适用于采用两级电压源转换器(VSC)的未来海上HVDC网络。