首页> 外文期刊>Science and Technology for the Built Environment >Effect of fittings on volumetric airflow measurements (RP-1245): Multiple-path (tee) duct disturbances
【24h】

Effect of fittings on volumetric airflow measurements (RP-1245): Multiple-path (tee) duct disturbances

机译:配件对体积气流测量的影响(RP-1245):多路径(三通)管道扰动

获取原文
获取原文并翻译 | 示例
   

获取外文期刊封面封底 >>

       

摘要

Current methods of making volumetric airflow measurements in the field are prone to a number of known inaccuracies because field technicians are required to take measurements in nonideal circumstances close to fitting disturbances. This is especially problematic when measurements are made in close proximity downstream of tee fittings as part of test and balancing procedures for HVAC systems designed to meet comfort and air quality requirements. The overall objectives of this research were (1) to quantify the influence of several duct disturbances on volumetric flow rate measurements and (2) to develop guidelines for field technicians to assist them in making more accurate volumetric airflow measurements in rectangular ducts during test and balance operations. Previous work has addressed the measurement issues associated with single-path duct disturbances. This article focusses on the error caused by multiple-path (diverging tee) duct disturbances. Measurements are presented of the error caused by the distance from tee fitting disturbances to a given airflow measurement (traverse) location. It is shown that in many situations, traverse measurements taken in the branch downstream of the tee are subject to significant regions of reverse flow, which cannot be sensed correctly by either pitot-static probes or hot-wire probes. In such situations, large airflow rate errors will be the result, and it is therefore recommended that alternative traverse positions be utilized in these circumstances.
机译:由于需要现场技术人员在接近装配干扰的非理想情况下进行测量,因此当前在现场进行体积气流测量的方法容易出现许多已知的误差。当在三通接头的下游非常近的位置进行测量以作为为满足舒适度和空气质量要求而设计的HVAC系统的测试和平衡程序的一部分时,这尤其成问题。这项研究的总体目标是(1)量化几种管道扰动对体积流量测量的影响,以及(2)为现场技术人员制定指南,以帮助他们在测试和平衡期间在矩形管道中进行更准确的体积空气流量测量操作。先前的工作已经解决了与单路径管道干扰相关的测量问题。本文重点介绍由多径(发散三通)管道扰动引起的误差。给出了从三通接头干扰到给定气流测量(横向)位置的距离所引起的误差的测量结果。结果表明,在许多情况下,在三通的下游分支中进行的导线测量都受到很大的逆流区域的影响,皮托管式探针或热线探针都无法正确检测到该区域。在这种情况下,将会导致较大的气流速率误差,因此建议在这些情况下使用其他的横向位置。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号