This study reports levels of indoor environmental quality variables before and after installation of heat recovery ventilation in a primary school located in an urban area in Izmir, Turkey. A CO2-based modeling was performed to determine the required flow rates that would comply with an international ventilation standard, followed by computational fluid dynamics modeling for best airflow distribution in a classroom. Temperature, CO2, PM2.5, and total volatile organic compounds were found at undesired levels, among which relative humidity, CO2, and PM2.5 were improved after the intervention. Reductions in the mean and maximum concentrations were 29% and 68% for CO2 and 29% and 46% for PM2.5. This intervention study was a part of the city-wide main project that aimed to increase awareness of the students and their families, teachers, and staff regarding importance of indoor environmental quality in both at school and home due to its possible effects on children's health and academic performance, one of the major challenges of today's societies all around the globe.
机译:本研究报告了在位于土耳其伊兹密尔市区城市地区的小学航空恢复通风前后的室内环境质量变量水平。进行了基于CO2的建模以确定符合国际通风标准的所需流速,然后是在教室中进行最佳气流分布的计算流体动力学建模。在干预后,在不需要的水平下发现温度,CO 2,PM2.5和总挥发性有机化合物,其中相对湿度,CO 2和PM2.5得到改善。对于PM2.5的CO 2和29%和46%,减少平均值和最大浓度为29%和68%,46%。这种干预研究是全市主要项目的一部分,旨在提高学生及其家庭,教师和员工的认识,这是由于其对儿童健康的可能影响而在学校和家庭中都有关于室内环境质量的重要性学术表现,全球各地社会的主要挑战之一。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号