首页> 外文会议>International conference on Frontiers of manufacturing science and measuring technology >FBG Displacement Sensor Application Research on Geology Security Monitoring of Substation
【24h】

FBG Displacement Sensor Application Research on Geology Security Monitoring of Substation

机译:FBG位移传感器在变电站地质安全监控中的应用研究

获取原文

摘要

The great area crack can cause the landslide of the substation sliding.Dislocation is the significant factor to reflect the crack.Embedded the mast structure of FBG displacement sensor,the relative displacement of retaining wall in YanJin substation can be obtained.Placed 3 FBG displacement sensors on the southeast comer of the substation downstream integrated the real-time monitoring system for the dislocation crack of YanJin substation downstream.In the monitoring results of the 479 days,daily average displacement of 3# sensor located in substation downstream maximized to 1.58mm on January 27th 2011; and daily average displacement of 2# sensor located in substation downstream minimized to-1.94mm on September 18th 2011.The monthly rainfall maximized to 123.5mm,70.7mm,75.9mm in July,August,September 2011 and minimized to 26.8mm,12.9mm,and 23.3mm in January 2011,November,December 2010.Considered local precipitation,cracks closely related to the local precipitation.
机译:大面积的裂缝会引起变电站的滑坡滑动。位移是反映裂缝的重要因素。将FBG位移传感器嵌入桅杆结构中,可以得到盐津变电站挡土墙的相对位移。放置3个FBG位移传感器在479天的监测结果中,位于变电站下游3#传感器的日平均位移在1月最大达到1.58mm。 2011年27日; 2011年9月18日位于变电站下游的2#传感器的日平均位移最小为-1.94mm。2011年7月,2011年9月,8月的月降雨量最大为123.5mm,70.7mm,75.9mm,最小为26.8mm,12.9mm。和2011年1月(2010年11月)的23.3毫米。考虑到局部降水,裂纹与局部降水密切相关。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
获取原文

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号