Among the detection methods of partial discharge in high voltage electrical equipment, optical method is new and competitive. This paper presents a diaphragm type optical fiber EFPI (External Fabry-Perot Interfering) sensor, which is developed by external Fabry-Perot interfering method and used for detection of partial discharge. We made a needle-plane electrode in oil, detected it with joint detection of optical fiber sensor and VHF (Very High Frequency) sensor. The study finds: optical fiber sensor can pick up signals effectively on PD (partial discharge) detection in early stage, have high sensitivity. The signal picked up by optical fiber sensor and VHF sensor not only has well correspondence, which can identify partial discharge signals effectively, but also has broad application, such as the on-line detection of transformer or other high voltage electrical equipment.
机译:在高压电气设备局部放电的检测方法中,光学方法是新的且具有竞争力。本文提出了一种膜片式光纤EFPI(外部法布里-珀罗干涉)传感器,该传感器是通过外部法布里-珀罗干涉法开发的,用于检测局部放电。我们在油中制成了针状平面电极,并通过光纤传感器和VHF(甚高频)传感器的联合检测对其进行了检测。研究发现:光纤传感器可以在早期的PD(局部放电)检测中有效地拾取信号,具有很高的灵敏度。光纤传感器和VHF传感器采集的信号不仅具有良好的对应关系,可以有效地识别局部放电信号,而且具有广泛的应用前景,例如变压器或其他高压电气设备的在线检测。