首页> 外文OA文献 >Cooling load calculations of radiant and all-air systems for commercial buildings
【2h】

Cooling load calculations of radiant and all-air systems for commercial buildings

机译:商业建筑的辐射和全空系统的冷负荷计算

摘要

The authors simulated in TRNSYS three radiant systems coupled with a 50% sized variable air volume (VAV) system and a 50% sized all-air VAV system with night ventilation. The objective of this study was to identify the differences in the cooling load profiles of the examined systems when they are sized based on different levels of the maximum cooling demand. The authors concluded that for high thermal mass radiant system nocturnal operation was adequate for providing an acceptable thermal environment even when the radiant system was sized based on the 50% of the maximum cooling demand. The 50% all-air system alone was able to provide comfort if night cooling was implemented. On the other hand, radiant cooling panels (low thermal mass) should be operating during the occupancy period. When sizing a high thermal mass radiant cooling system, the effect of thermal inertia and the response time should always be taken into account.
机译:作者在TRNSYS中模拟了三个辐射系统,以及50%大小的可变风量(VAV)系统和50%大小的具有夜间通风的全空气VAV系统。这项研究的目的是,根据最大冷却需求的不同水平确定被检查系统的制冷负荷曲线时,要确定它们的差异。作者得出结论,对于高热质量的辐射系统,夜间运行足以提供可接受的热环境,即使辐射系统的大小基于最大冷却需求的50%而定。如果实施夜间冷却,仅50%的全空气系统就能提供舒适感。另一方面,在使用期间应使用辐射散热面板(低热量)。在确定高热质量辐射冷却系统的尺寸时,应始终考虑热惯性和响应时间的影响。