摘要

Due to the increasing penetration of single-phase small generation units and electric vehiclesconnected to distribution grids, system operators are facing challenges related to local unbalanced voltagerise or drop issues, which may lead to a violation of the allowed voltage band. To address this problem,distribution transformers with on-load tapping capability are under development. This paper presentsmodel and experimental validation of a 35 kVA three-phase power distribution transformer with independent on-load tap changer control capability on each phase. With the purpose of investigating andevaluating its effectiveness under different operative conditions, appropriate scenarios are defined andtested considering both balanced and unbalanced situations, also in case of reverse power flow. Theexperimental setup is built starting from an analysis of a Danish distribution network, in order toreproduce the main feature of an unbalanced grid. The experimental activities are recreated in by carryingout dynamics simulation studies, aiming at validating the implemented models of both the transformer aswell as the other grid components. Phase-neutral voltages’ deviations are limited, proving the effectiveness of the phase-independent tap operations. Furthermore, minor deviations of the results from simulations and experiments confirm that all the system components have been properly modelled.
机译:由于单相小型发电机组和连接到配电网的电动汽车的普及率不断提高,系统运营商面临着与局部不平衡电压上升或下降问题有关的挑战,这可能导致违反允许的电压范围。为了解决这个问题,正在开发具有有载分接能力的配电变压器。本文介绍了在每相上具有独立的有载分接开关控制能力的35 kVA三相配电变压器的模型和实验验证。为了调查和评估其在不同操作条件下的有效性,定义并测试了平衡和不平衡情况下的合适方案,并进行了测试,并且在发生逆潮流时也是如此。为了重现不平衡电网的主要特征,从丹麦配电网的分析开始建立实验装置。通过进行动力学仿真研究来重新创建实验活动,旨在验证变压器以及其他电网组件的实现模型。相中性电压的偏差是有限的,证明了与相无关的抽头操作的有效性。此外,仿真和实验结果的微小偏差证实所有系统组件均已正确建模。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号