Parametric analysis of the operation of nocturnal radiative cooling panels coupled with in room PCM ceiling panels

机译:夜间辐射冷却板与室内pCm天花板相结合的参数分析

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

The scope of this parametric simulation study was to identify the optimal combination of set-points for different parameters of a radiant PCM ceiling panels cooling system that will result in the best indoor thermal environment with the least possible energy use. The results showed that for each parameter examined, a different set-point value was optimal for the thermal environment than the value that was optimal for the reduction of energy use. Therefore, two additional simulations were run, one with the combination of set-point values that resulted in the improvement of the thermal environment and one with the set-point values resulting in the reduction of energy use. In the first case, the temperature was within the range of Category III of EN 15251 (23 – 26°C, 73.4 – 78.8°F) for 83.5% of the occupancy time, while in the second case it was within Category III for 39.4%. In the first simulation, the energy usage of the pumps and the heat pump was 178 kWh, 608 kBtu, while for the second one it was 36 kWh, 121 kBtu. It was concluded that the optimal combination of set-point values to provide the most comfortable thermal environment was to activate the pump circulating water to the PCM no earlier than 03:00 and get activated when the temperature in the storage tank was below 21°C, 69.8°F, activate the heat pump no earlier than 05:00 and get activated when the temperature in the storage tank was below 15°C, 59°F, and lastly have a temperature difference between the output of the solar panels and the temperature in the middle of the storage tanks of 5 K, 9°F.
机译:此参数模拟研究的范围是针对辐射PCM天花板冷却系统的不同参数确定设定点的最佳组合,这将以尽可能少的能源使用产生最佳的室内热环境。结果表明,对于每个检查的参数,对于热环境而言,最佳设定值与对于减少能源消耗而言最佳设定值不同。因此,运行了另外两个模拟,一个模拟与设定点值相结合,从而改善了热环境,另一个模拟与设定点值相结合,从而减少了能耗。在第一种情况下,温度在EN 15251的III类范围内(23 – 26°C,73.4 – 78.8°F),占占用时间的83.5%,而在第二种情况下,温度在III类的范围内为39.4。 %。在第一个模拟中,泵和热泵的能耗为178 kWh,608 kBtu,第二个模拟为36 kWh,121 kBtu。得出的结论是,提供最舒适的热环境的设定点值的最佳组合是在不早于03:00时将泵循环水激活到PCM,并在储罐中的温度低于21°C时被激活。 ,温度为69.8°F,请在05:00之前启动热​​泵,并在储罐温度低于15°C(59°F)时启动,最后在太阳能电池板的输出与储罐中间的温度为5 K,9°F。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号