摘要

This paper presents a numerical study of a regenerative indirect evaporative cooler, the so-called Dew Point Cooler (DPC), which is part of a Desiccant Cooling system that may both dehumidify and cool humid air. The DPC model is based on first principles using a 1D finite volume scheme and determines the steady state working conditions for the component. A sensitivity analysis of the DPC performance is carried out based on the air inlet conditions, air flow rate and recirculation fraction. A recirculation fraction around 0.3 maximizes the DPC net cooling capacity. The supply temperature is found to be mostly affected by the inlet humidity ratio. Manufacturer data are used to tune the model. The tuned DPC model is characterized by an area effectiveness coefficient which is kept constant at 0.55. The cooling capacity and water consumption estimated by the tuned model deviate within 3% and 8%, respectively from manufacturer data. The computed pressure drops deviates within 6% from manufacturer data.
机译:本文介绍了一种蓄热式间接蒸发式冷却器的数值研究,即所谓的露点冷却器(DPC),它是干燥剂冷却系统的一部分,该系统既可以除湿又可以冷却湿空气。 DPC模型基于使用1D有限体积方案的第一原理,并确定组件的稳态工作条件。 DPC性能的灵敏度分析是基于进气条件,空气流速和再循环分数进行的。约0.3的再循环分数可使DPC净冷却能力最大化。发现供应温度主要受入口湿度比的影响。制造商数据用于调整模型。调整后的DPC模型的特征在于区域有效系数保持恒定在0.55。调整后的模型估计的制冷量和耗水量分别与制造商数据相差3%和8%。计算得出的压降与制造商数据的偏差在6%以内。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号