首页> 外文OA文献 >Decreasing the commutation failure frequency in HVDC transmission systems
【2h】

Decreasing the commutation failure frequency in HVDC transmission systems

机译:降低HVDC传输系统中的换向失败频率

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

In this paper we show how a fairly large proportion of those commutation failures that are due to single-phased short circuits to earth can be avoided. In a control circuit based on a digital signal processor (DSP) it is possible, with instantaneous results, to switch from a normal control strategy with equidistant firing pulses to a strategy that takes into consideration the potentially dangerous voltage changes on the supply lines, If the supply voltages are monitored continuously, it is possible to calculate the necessity of advancing the firing pulses to avoid commutation failures. In the paper such a calculation technique is described. The monitoring times may be approximately 50 μsec apart corresponding to a distance of 0.016 radians or about 1.
机译:在本文中,我们展示了如何避免由于对地单相短路而导致很大比例的换向失败。在基于数字信号处理器(DSP)的控制电路中,有可能即时产生结果,从具有等距触发脉冲的正常控制策略切换到考虑电源线上潜在危险电压变化的策略。如果对电源电压进行连续监控,则可以计算出提前触发脉冲以避免换向失败的必要性。在本文中,描述了这种计算技术。监视时间可能相隔约50微秒,对应于0.016弧度的距离或约1。