How to Improve Cloud Services Availability? Investigating the Impact of Power and It Subsystems Failures

机译:如何提高云服务可用性?调查电源及其子系统故障的影响

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

The cloud data center is a complex system composed of power, cooling, and IT subsystems. The power subsystem is crucial to feed the IT equipment. Power disruptions may result in service unavailability. This paper analyzes the impact of the power subsystem failures on IT services regarding different architecture configurations based on TIA-942 standard such as non-redundant, redundant, concurrently maintainable, and fault tolerant. We model both subsystems, power and IT, through Stochastic Petri Net (SPN). The availability results show that a fault tolerant power and IT configuration reduces the downtime from 54.1 to 34.5 hours/year when compared to a non-redundant architecture. The sensibility analysis results show that the failure and repair rates of the server component in a fault tolerant system present the highest impact on overall data center availability.
机译:云数据中心是一个由电源,散热和IT子系统组成的复杂系统。电源子系统对于为IT设备供电至关重要。电源中断可能会导致服务不可用。本文分析了基于TIA-942标准的不同体系结构配置(例如非冗余,冗余,可同时维护和容错)的电源子系统故障对IT服务的影响。我们通过随机Petri网(SPN)对电源和IT子系统进行建模。可用性结果表明,与非冗余架构相比,容错电源和IT配置将停机时间从每年54.1减少到34.5小时/年。敏感性分析结果表明,容错系统中服务器组件的故障率和修复率对整个数据中心的可用性影响最大。