Evaluation of Silicone Rubber Insulators used in High-Voltage Transmission Lines

机译:高压输电线路用硅橡胶绝缘子的评价

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

Three long-rod silicone rubber composite insulators used in 230 kV power transmission lines were evaluated for aging affects. The insulators were obtained from various outdoor desert locations within Saudi Arabia where they had been in service for 6 years. Surface degradation associated with the aging process was analyzed by using Scanning Electron Microscopy (SEM) coupled with Energy Dispersive X-ray Spectroscopy (EDS), Fourier Transform Infra-Red Spectroscopy (FTIR), and Electron Spectroscopy for Chemical Analysis (ESCA). Electrical performance of insulators was evaluated by Rapid Flashover Voltage Tests (RFVT) and Pollution Severity Measurement Tests. Depending on their locations of service, the samples exhibited various types of pollutants at their surfaces. The analysis indicated that the insulator material showed localized surface degradation while there was no evidence of micro-cracking. Furthermore, it was noted that the electrical performance of the insulators was not significantly affected by exposure during the in-service period.
机译:评估了230 kV输电线路中使用的三种长杆硅橡胶复合绝缘子的老化影响。绝缘子是从在沙特阿拉伯服务了6年的沙特阿拉伯各个室外沙漠地点获得的。通过使用扫描电子显微镜(SEM)结合能量色散X射线光谱(EDS),傅立叶变换红外光谱(FTIR)和化学分析电子光谱(ESCA)分析与老化过程相关的表面降解。绝缘子的电气性能通过快速闪络电压测试(RFVT)和污染严重度测试进行了评估。根据服务地点的不同,样品的表面会显示出各种类型的污染物。分析表明,绝缘子材料表现出局部表面退化,而没有微裂纹的迹象。此外,注意到在使用期间,绝缘体的电性能并未受到暴露的显着影响。

著录项

  • 作者

    Ul-Hamid Anwar;

  • 作者单位
  • 年度 2008
  • 总页数
  • 原文格式 PDF
  • 正文语种
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号