摘要

Internal arc fault tests are important for ensuring the safety of medium-voltage metal-enclosed switchgears. Since these tests are conducted at full scale, the costs of the test objects as well as the high-power laboratory are significant. This paper presents an experimental study to clarify whether such tests can be simplified by downscaling. Tests with volume and energy downscaled to 1/3 and 1/10, respectively, were performed on a single-phase arrangement with air as the insulating gas. The test results showed that the internal pressure rise caused by the arc can be reproduced well using a smaller compartment and lower current. The potential damage caused by the exhaust of the hot gas escaping through the pressure-relief openings is more challenging to predict from small-scale tests.
机译:内部电弧故障测试对于确保中压金属封闭式开关设备的安全性很重要。由于这些测试是全面进行的,因此测试对象以及大功率实验室的成本都很高。本文提出了一项实验研究,以阐明是否可以通过缩小规模简化此类测试。在以空气为绝缘气体的单相装置上,分别进行了体积和能量缩减至1/3和1/10的测试。测试结果表明,使用较小的隔室和较低的电流可以很好地再现电弧引起的内部压力上升。从小型泄压孔逸出的高温气体排出造成的潜在损害更具挑战性。