Uninterruptible Power Supply menggunakan flyback converter sebagai PFC Converter

机译:不间断电源使用反激式转换器作为pFC转换器

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

UPS is the equipment used to provide temporary resources as the main source of outages. The loss of the UPS is able to reduce the power factor and generate harmonics. To overcome these problems added to the UPS power factor correction. In this UPS, power factor correction is placed in the charger using a flyback converter. Flyback converter must work in conditions discontinuous, because the condition is discontinuous value of magnetizing inductance (Lm) is small, so that the impedance value is assumed nearly equal to the value detainees who are resistive (R). UPS is tested using a lamp and ballast. Power factor is measured from a small current (1.09 A) to the maximum current (2.5 A) increased from 0.86 to 0.93. While the harmonics that appear decreased from 49.5% to 41.45%. From the test impedance values can not be assumed equal to zero.
机译:UPS是用于提供临时资源的主要设备,这些资源是中断的主要来源。 UPS的损耗能够降低功率因数并产生谐波。为了克服这些问题,UPS功率因数校正中增加了。在此UPS中,使用反激转换器将功率因数校正放置在充电器中。反激转换器必须在不连续的条件下工作,因为该条件是不连续的,励磁电感(Lm)的值很小,因此假定阻抗值几乎等于电阻(R)的被拘留者的值。 UPS已使用灯泡和镇流器进行了测试。功率因数从小电流(1.09 A)到最大电流(2.5 A)从0.86增加到0.93。而出现的谐波从49.5%降至41.45%。从测试阻抗值不能假定等于零。