The effect of inrush transients on pv inverter's grid impedance measurement based on inter-harmonic injection

机译:基于间谐波注入的涌流瞬变对光伏逆变器电网阻抗测量的影响

摘要

This paper addresses a cause for false tripping of photovoltaic inverters with antiislanding protection based on impedance measurement with inter-harmonic injection. Earlier discussions about tripping problems happening when several devices are doing the measurement at the same time are supplemented with a problem caused by inrush transients of nearby devices. A series of experiments was conducted in the Power Quality laboratory of the TU/e, on a PV inverter which complies with the DIN VDE 0126 standard. Impedance measurement was done in parallel with the inverter and measurement results are presented. A criterion for false tripping caused by transients is explored. Also, influences of network impedance and grid harmonic pollution on false tripping were analyzed. In the end, some signal processing techniques are proposed to avoid this problem.
机译:本文基于谐波间注入的阻抗测量,解决了带有反孤岛保护的光伏逆变器误跳闸的原因。先前有关在几个设备同时进行测量时发生跳闸问题的讨论中,还补充了附近设备的浪涌瞬变引起的问题。在TU / e的电能质量实验室中,对符合DIN VDE 0126标准的PV逆变器进行了一系列实验。与逆变器并行进行阻抗测量,并给出测量结果。探索了由瞬态引起的误跳闸的标准。此外,分析了网络阻抗和电网谐波污染对误跳闸的影响。最后,提出了一些信号处理技术来避免此问题。