首页> 外文OA文献 >Comparison of the linear approximations for the dynamic security region of network-reduction power systems
【2h】

Comparison of the linear approximations for the dynamic security region of network-reduction power systems

机译:网络还原电力系统动态安全域线性近似的比较

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

The Dynamic Security Region (DSR) of bulk power system has been accepted more and more in recent years for providing plenty of security information and good prospect in online application. This paper compares three linear approximations for the dynamic security region of network-reduction power systems. The three linear approximations are the Q-linear approximation based on the quadratic approximation of stability region, the L-linear approximation based on the linear approximation of stability region and the LOlinear approximation based on the invariant assumption of the normal vector for the boundary of the stability region corresponding to different control variable. The three linear approximations are all obtained with a same critical point lying just on the boundary of dynamic security region. The critical point is searched with numerical simulation. The accuracy of the three linear approximations is compared, using the linear approximation obtained with the curve fitting approach or the actual boundary of DSR searched as the benchmark. Simulation results in IEEE 3-machine 9-bus system and 10-machine 39-bus New England system show that all the three linear approximations display fairly accurate estimation. Furthermore, from the computational viewpoint, the L-linear and the L0-linear method are two alternative choices to approximate the dynamic security region. © 2006 IEEE.
机译:近年来,大容量电力系统的动态安全区域(DSR)已被越来越多的人接受,因为它提供了大量的安全信息并在在线应用中具有良好的前景。本文比较了减少网络的电力系统的动态安全区域的三种线性近似。这三个线性近似是基于稳定区域二次近似的Q线性近似,基于稳定区域线性近似的L线性近似和基于法向向量边界不变法则不变假设的LOlinear近似。稳定区域对应于不同的控制变量。三个线性近似值都是在动态安全区域边界上具有相同临界点的情况下获得的。通过数值模拟搜索临界点。使用以曲线拟合法或搜索的DSR实际边界为基准的线性近似值,比较了三个线性近似值的精度。在IEEE 3机9总线系统和10机39总线New England系统中的仿真结果表明,所有三个线性近似值都显示出相当准确的估计值。此外,从计算角度来看,L线性和L0线性方法是近似动态安全区域的两个替代选择。 ©2006 IEEE。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号