Leakages are a relevant issue in water distribution networks with severe effects on costs and water savings. While there are several solutions for detecting leakages by analyzing of the minimum night flow and the pressure inside manageable areas of the network (DMAs), the problem of estimating the time-instant when the leak occurred has been much less considered. However, an estimate of the leakage time-instant is useful for the diagnosis operations, as it may clarify the leak causes. We here address this problem by combining two change-point methods (CPMs) in a hierarchy: at first, a CPM analyses the minimum night flow providing an estimate of the day when the leakage started. Such an estimate is then refined by a second CPM, which analyzes the residuals between the pressure measurements and a network model in a neighborhood of the estimated leakage day. The proposed approach was tested on data from a DMA of a big European city, both on artificially injected and real leakages. Results show the feasibility of the proposed solution, also when leakages are very small. © IFIP International Federation for Information Processing 2013.
机译:漏水是配水网络中的一个相关问题,会对成本和节水产生严重影响。尽管有几种解决方案可以通过分析最小夜间流量和网络可管理区域(DMA)内的压力来检测泄漏,但考虑泄漏发生时的即时估计问题却少了很多。但是,泄漏时间瞬时值的估计对于诊断操作很有用,因为它可以澄清泄漏原因。在这里,我们通过在层次结构中组合两个变更点方法(CPM)解决此问题:首先,CPM分析最小夜间流量,以提供泄漏开始日期的估计。然后,通过第二个CPM完善这种估计,该CPM分析估计的泄漏日附近压力测量值和网络模型之间的残差。在来自欧洲大城市DMA的数据上对提出的方法进行了测试,包括人为注入和实际泄漏。结果表明了该方案的可行性,即使泄漏量很小。 ©IFIP国际信息处理联合会2013。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号