首页> 外文OA文献 >R-407H as drop-in of R-404A. Experimental analysis in a low temperature direct expansion commercial refrigeration system
【2h】

R-407H as drop-in of R-404A. Experimental analysis in a low temperature direct expansion commercial refrigeration system

机译:R-407H作为R-404a的插入物。低温直接膨胀商用制冷系统的实验分析

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

This work analyses experimentally the possibility of using the reduced GWP refrigerant R-407H (HFC family, GWP = 1378) as drop-in substitute of R-404A (HFC family, GWP = 3945) in low temperature centralized direct expansion refrigeration system. The experimental plant and the test methodology are described. It covered top up or partial drop-in and energy consumption tests at −20 °C of product temperature and 25, 35 and 45 °C of condensing temperature using a small-scale supermarket under laboratory conditions. It has been measured that the use of R-407H instead of R-404A is favourable from the point of view of energy efficiency. Reductions in the energy consumption of up to 7.7% (compressor) and 4.0% (whole system) have been measured. However, there is an increment in the compressor's discharge temperature of up to 13.8 K. In addition, the operation of the system with both refrigerants was correct.
机译:这项工作通过实验分析了在低温集中式直接膨胀制冷系统中使用还原型GWP制冷剂R-407H(HFC系列,GWP = 1378)作为R-404A(HFC系列,GWP = 3945)的直接替代品的可能性。描述了实验工厂和测试方法。它涵盖了在小型实验室条件下使用小型超级市场在产品温度-20°C和冷凝温度25、35和45°C下的补充或部分投入和能耗测试的范围。从能量效率的角度,已经测量到使用R-407H代替R-404A是有利的。据测量,能耗降低了多达7.7%(压缩机)和4.0%(整个系统)。但是,压缩机的排气温度最高可升高13.8 K,此外,使用两种制冷剂的系统运行都是正确的。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号