首页> 外文OA文献 >Experimental analysis of the internal heat exchanger influence on a vapour compression system performance working with R1234yf as a drop-in replacement for R134a
【2h】

Experimental analysis of the internal heat exchanger influence on a vapour compression system performance working with R1234yf as a drop-in replacement for R134a

机译:R1234yf作为R134a的直接替代品,内部换热器对蒸汽压缩系统性能影响的实验分析

摘要

This paper presents an experimental analysis of the influence of an internal heat exchanger on the performance of a vapour compression system using R1234yf as a drop-in replacement for R134a. In this work, we compare the energy performance of a monitored vapour compression system using both refrigerants, R134a and R1234yf, with and without the presence of an internal heat exchanger under a wide range of working conditions. A set of experimental tests are carried out varying the condensing temperature, the evaporating temperature and the internal heat exchanger use. From the experimental results, reductions in cooling capacity and COP between 6 and 13% have been observed when R134a is replaced by the drop-in fluid R1234yf, although the presence of an IHX can help to lessen these reductions between 2 and 6%. Finally, the experimental results obtained agree with the theoretical evaluations developed neglecting the pressure drops.
机译:本文介绍了一个内部热交换器对使用R1234yf替代R134a的蒸汽压缩系统性能的影响的实验分析。在这项工作中,我们比较了在多种工作条件下使用和不使用内部热交换器的情况下,同时使用制冷剂R134a和R1234yf的受监控蒸汽压缩系统的能量性能。进行了一系列的实验测试,以改变冷凝温度,蒸发温度和内部热交换器的使用。从实验结果可以看出,当用滴入式流体R1234yf代替R134a时,冷却能力和COP降低了6%到13%,尽管IHX的存在可以帮助减少2%和6%之间的降低。最后,所获得的实验结果与忽略压降的理论评估相吻合。