Field measurement of airborne particulate matters concentration in a hospital's operating room

机译:医院手术室中空气中颗粒物浓度的现场测量

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

In a hospital operating room, adequate air flow and cleanliness are crucial to protect the patient from surgical site infection (SSI) during a procedure. The probability of the patient to get the infection is related to the concentration of bacteria carrying particles inside the room. This paper presents a field measurement study to quantify the concentration of particulate matters (PM) in a hospital operating room which complies with the ISO Class 7 requirements. The operating room was equipped with High Efficiency Particulate Air (HEPA) filters and a vertical laminar air flow (LAF) system. The measurements were conducted at three height levels from the floor namely 1.2 m, 1.8 m and 2.4 m. The data was logged at a rest condition, in accordance to the ISO 14644-1 requirements. A HPC300 particle counter was used to measure the concentrations of particulate matters namely PM0.5, PM1 and PM5. The results show that the concentrations of all particulate matters were higher at the height level of 1.2 m compared to other height levels. The concentration of PM0.5 was relatively higher than PM1 and PM5 in the vicinity of operating table.
机译:在医院的手术室中,足够的空气流通和清洁对于保护患者在手术过程中免受手术部位感染(SSI)至关重要。患者被感染的可能性与房间内携带颗粒的细菌浓度有关。本文提出了一项现场测量研究,以量化符合ISO 7级要求的医院手术室中颗粒物(PM)的浓度。手术室配备了高效微粒空气(HEPA)过滤器和垂直层流(LAF)系统。在距地面三个高度级别(即1.2 m,1.8 m和2.4 m)进行测量。根据ISO 14644-1要求,在静止状态下记录数据。使用HPC300粒子计数器测量颗粒物(即PM0.5,PM1和PM5)的浓度。结果表明,与其他高度相比,在1.2 m高度处所有颗粒物的浓度均较高。在手术台附近,PM0.5的浓度相对高于PM1和PM5。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号