Insulation coordination study for a substation requires accurate prediction of possible overvoltages generated within or external to the substation. Protective devices in the form of surge arresters are usually installed to protect substation equipment from overvoltages caused by both switching and lightning surges. In this work, the decision whether to install or not to install ZnO surge arresters for power transformer protection in a 132 kV GIS substation was made with the aid of ATP-EMTP software. Various models such as those for underground cables and ZnO surge arresters were carefully studied since the results of the simulation study were very much dependent on the models chosen. The resulting overvoltages at the power transformer due to possible lightning impulses at various injections points were studied. A decision was finally made based on the simulation results.
机译:变电站的绝缘协调研究需要准确预测变电站内部或外部可能产生的过电压。通常安装避雷器形式的保护装置,以保护变电站设备免受开关和雷电浪涌引起的过电压的影响。在这项工作中,借助ATP-EMTP软件决定是否在132 kV GIS变电站中安装或安装用于变压器保护的ZnO避雷器。由于模拟研究的结果很大程度上取决于所选模型,因此对各种模型(例如地下电缆和ZnO电涌放电器的模型)进行了仔细研究。研究了由于在各个注入点可能产生的雷电脉冲而在电源变压器上产生的过电压。最后根据仿真结果做出决定。