首页> 外文OA文献 >Magnetostriction assessment of power transformer (a case study of 30/40MVA, 132/33 kV transformer at Bauchi substation)
【2h】

Magnetostriction assessment of power transformer (a case study of 30/40MVA, 132/33 kV transformer at Bauchi substation)

机译:电力变压器的磁致伸缩评估(以包奇变电站的30 / 40MVA,132/33 kV变压器为例)

摘要

A lot of things determine the life expectancy of a transformer such as overheating due to triplen harmonics, unbalanced loading, vibro-acoustic noise and so on. For this reason, this paper presents the investigation carried out on the magnetostrictive sound of Bauchi, 30/40 MVA, 132/33 KV substation transformer. Readings were taken using standard audio recording instrument for various loading and voltage conditions in the mornings, afternoons and nights for six days and the offline assessment was carried out using digital spectrum analyzer. However, no access could be gained to the variation of certain important parameters, like changing of core dimensions, loosing or tightening of core and so on, for the substation transformer in-situ in the substation hence separate laboratory test transformers were used in the assessment of the effect of core damping pressure, construction looseness and transformer saturation on the vibro-acoustic noise. Conclusively, increasing the operation voltage of transformer tends to produce more magnetostriction effect while loosening core lamination increases the energy losses.
机译:许多因素决定了变压器的预期寿命,例如由于三次谐波,不平衡负载,振动声噪声等导致的过热。因此,本文介绍了对Bauchi,30/40 MVA,132/33 KV变电站变压器的磁致伸缩声的研究。使用标准的音频记录仪在早晨,下午和晚上的六天时间内读取各种负载和电压条件的读数,并使用数字频谱分析仪进行离线评估。但是,对于变电站中的变电站变压器,无法获得某些重要参数的变化,例如更改铁芯尺寸,松动或拧紧铁芯等,因此在评估中使用了单独的实验室测试变压器阻尼力,结构松动和变压器饱和对振动声噪声的影响。总之,增加变压器的工作电压往往会产生更大的磁致伸缩效果,而松散的铁心叠片则会增加能量损耗。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号