Improvement of the indoor thermal environment over pilotis of RC buildings

机译:改善RC建筑物的中庭上方的室内热环境

摘要

In winter, surface temperature of indoor floors that cover outdoor pilotis is often too low for persons to work for a long time. In this research we tried to improve indoor thermal environment in meeting rooms on bridges that connected northern and southern buildings of Niigata Institute of Technology, Kashiwazaki, Niigata, JPN, by using floor carpets. We showed that thermal loss from floor surface to pilotis was greatly reduced because of large thermal resistance of carpets. And also we clarified that estimation of air temperature in closed spaces between ceiling panels over pilotis and floors of upper rooms was possible by using observed data of outdoor air temperature in pilotis.
机译:在冬季,覆盖室外领口的室内地板的表面温度通常太低,无法长时间工作。在这项研究中,我们试图通过使用地板地毯来改善连接新泻工学院北泻和新泻理工学院,日本新泻市柏崎市南北建筑物的桥梁会议室的室内热环境。我们表明,由于地毯的大热阻,从地板表面到中庭的热损失大大减少了。并且我们还阐明了,通过使用在领口的室外空气的观测数据,可以估计领口上方的顶板与上层房间的地板之间的封闭空间中的空气温度。