Energy performance of air-to-water and water-to-water heat pumps in hotel applications

机译:酒店应用中的空气对水和水对水热泵的能源性能

摘要

We present work on measurement of the energy performance of heat pumps for hotel operations in subtropical climates. Two city hotels in Hong Kong were investigated. The first case was an application of an air-to-water heat pump to provide heating for an outdoor swimming pool during the heating season. The second case was the installation of three water-to-water heat pumps to complement an existing boiler system for hot water supply. The heating energy output and corresponding electricity use were measured. The heat pump energy efficiency was evaluated in terms of the coefficient of performance (COP), defined as the heating energy output to the electrical energy use. The air-to-water heat pump provided 49.1 MWh heating while consuming 24.6 MWh electricity during the 612-month heating season from mid-October to April. For the water-to-water heat pumps, the estimated annual heating output and the electricity use were 952 and 544 MWh, respectively. It was found that the heat pumps generally operated in a COP range of 1.5-2.4, and the payback period was about two years, which was considered financially attractive.
机译:我们介绍了在亚热带气候下用于酒店运营的热泵能源性能测量的工作。对香港的两家城市酒店进行了调查。第一种情况是应用空气-水热泵在供暖季节为室外游泳池供热。第二种情况是安装了三个水对水热泵,以补充现有的热水供应锅炉系统。测量了热能输出和相应的用电量。根据性能系数(COP)评估热泵能效,该系数定义为输出到电能使用的热能。从10月中旬到4月,在612个月的供暖季节中,空气-水热泵提供了49.1 MWh的供暖,同时消耗了24.6 MWh的电力。对于水对水热泵,估计的年供热量和用电量分别为952和544 MWh。发现热泵通常在COP范围为1.5-2.4的范围内运行,投资回收期约为两年,这被认为在财务上具有吸引力。

著录项

  • 作者

    Lam JC; Chan WW;

  • 作者单位
  • 年度 2003
  • 总页数
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号