摘要

Sizing of horizontal ceiling vent in a tall atrium is usually based on vent flow models with unidirectional flow. This is only good for natural vents with large pressure differences between inside and outside. For low pressure differential across the horizontal ceiling vent as experienced in some atrium fires, bidirectional smoke flow rates were observed. The extraction rate through the vent would be reduced, giving poor performance of the smoke exhaust system. Bidirectional flow across a ceiling vent will be discussed in this paper. Models available in the literature will be briefly reviewed first. A new model was developed on studying effects of bidirectional flow across a horizontal vent on the smoke layer interface height. A critical pressure difference between inside and outside across the vent can be estimated on inducing bidirectional flows. The approach is illustrated with an example sizing calculation for a cubic atrium commonly found in Hong Kong.
机译:高中庭水平天花板通风口的尺寸通常基于具有单向流动的通风口流量模型。这仅适用于内部和外部之间压力差较大的自然通风孔。在某些中庭火灾中,由于水平天花板通风口的压差较低,因此观察到双向烟气流量。通过通风孔的抽气速度将降低,从而使排烟系统的性能下降。本文将讨论穿过天花板通风口的双向流动。首先简要回顾文献中可用的模型。开发了一种新模型,用于研究水平通风口上的双向流动对烟层界面高度的影响。可以通过诱导双向流动来估计通气孔内部和外部之间的临界压力差。通过在香港常见的立方中庭的尺寸计算示例说明了该方法。