Many central cooling systems in air-conditioned buildings have multiple chillers to meet various cooling load requirements. This paper further develops optimum load sharing strategies for the chillers in order to maximize their aggregate coefficient of performance (COP). Based on the part load performance curves of air-cooled screw chillers, it is ascertained that for two equally sized chillers operating, one should carry a full load and the other should be partially loaded to meet the system load. When two chillers of different sizes are running, the larger chiller should be fully loaded and the smaller chiller should operate at part load in order that their combined capacity satisfies the system load. Such an uneven load sharing strategy for achieving maximum COP is independent of ambient conditions and the control of condensing temperature. The variable primary flow of chilled water should be applied to chillers in order to implement the strategy. The results of this paper are useful in developing low-energy chiller plants.
机译:空调建筑物中的许多中央冷却系统都有多个冷却器,以满足各种冷却负荷的要求。本文进一步为冷水机开发了最佳的负载分担策略,以最大程度地提高其综合性能系数(COP)。根据风冷螺杆式冷水机组的部分负荷性能曲线,可以确定,对于两台同等大小的冷水机组,一台应承担满负荷,另一台应部分负荷以满足系统负荷。当运行两个不同大小的冷水机时,较大的冷水机应完全装满,较小的冷水机应在部分负载下运行,以使它们的总容量满足系统负载。用于实现最大COP的这种不均衡的负载分配策略与环境条件和冷凝温度的控制无关。为了实施该策略,应将可变的一次冷却水流量应用于冷却器。本文的结果对于开发低能耗冷水机组非常有用。

著录项

  • 作者

    Yu FW; Chan KT;

  • 作者单位
  • 年度 2007
  • 总页数
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号