首页> 外文OA文献 >Tune up of the set point of condensing temperature for more energy efficient air cooled chillers
【2h】

Tune up of the set point of condensing temperature for more energy efficient air cooled chillers

机译:调节冷凝温度的设定点,以实现更节能的风冷式冷水机组

摘要

This paper presents how to tune up the set point of the condensing temperature for improving the coefficient of performance (COP) of air cooled chillers under various operating conditions. The thermodynamic model of an air cooled screw chiller was developed using the simulation program TRNSYS and validated using the operating data and specifications of the chiller. A new configuration of variable speed condenser fans was proposed for the chiller. An algorithm was introduced to make use of a set point of condensing temperature to determine the number and speed of condenser fans staged at any given cooling capacity. A model was used to investigate how the COP changes with various set points of condensing temperature. It was found that the optimum set point for maximum COP is a function of outdoor temperature and chiller load. Depending on the operating conditions, the COP could increase by 12.1-110.4% when the variable speed condenser fans and the optimum set point of condensing temperature were applied to the existing air cooled screw chillers. This provides important insights into the development of more energy efficient air cooled chillers.
机译:本文介绍了如何调节冷凝温度的设定点,以提高在各种工况下的空气冷却式冷水机组的性能系数(COP)。使用模拟程序TRNSYS开发了风冷螺杆式冷水机的热力学模型,并使用了冷水机的运行数据和规格对其进行了验证。提出了一种用于冷却器的变速冷凝器风扇的新配置。引入了一种算法,该算法利用冷凝温度的设定点来确定在任何给定的冷却能力下分级冷凝器风扇的数量和速度。使用一个模型来研究COP如何随着冷凝温度的不同设定值而变化。发现最大COP的最佳设定点是室外温度和冷水机组负荷的函数。根据运行条件,将变速冷凝器风扇和最佳冷凝温度设定值应用于现有的风冷螺杆式冷水机组时,COP可以提高12.1-110.4%。这为开发更节能的风冷式冷水机提供了重要的见识。

著录项

  • 作者

    Yu FW; Chan KT;

  • 作者单位
  • 年度 2006
  • 总页数
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号