首页> 外文OA文献 >Study on performance correlations of an indirect evaporative cooler with condensation from primary airflow
【2h】

Study on performance correlations of an indirect evaporative cooler with condensation from primary airflow

机译:间接蒸发冷却器与一次气流冷凝的性能相关性研究

摘要

An analytical model of the heat and mass transfer performance of an indirect evaporative cooling system with condensation from primary airflow is developed in this paper. Different forms of heat transfer effectiveness have been defined, which can be used to calculate the outlet temperatures of the two airstreams. The fraction of condensation area to the total heat transfer area FA is proposed, which is an important parameter in the energy performance simulation of the installation. A complete set of independent dimensionless parameters that affect the overall performance of the heat exchanger has been developed as well. The influence of these parameters on the effectiveness and FA is discussed. Finally, an experimental comparison is presented for validating part of the simulation model.
机译:本文建立了具有主要气流凝结的间接蒸发冷却系统的传热和传质性能的分析模型。已经定义了不同形式的热传递效率,其可以用于计算两个气流的出口温度。提出了冷凝面积占总传热面积FA的比例,这是设备能量性能模拟中的重要参数。还开发了影响热交换器整体性能的一套完整的独立无量纲参数。讨论了这些参数对有效性和FA的影响。最后,进行了实验比较,以验证仿真模型的一部分。