首页> 外文OA文献 >Thermodynamic-behaviour model for air-cooled screw chillers with a variable set-point condensing temperature
【2h】

Thermodynamic-behaviour model for air-cooled screw chillers with a variable set-point condensing temperature

机译:设定点冷凝温度可变的风冷螺杆式制冷机的热力学行为模型

摘要

This paper presents a thermodynamic model to evaluate the coefficient of performance (COP) of an air-cooled screw chiller under various operating conditions. The model accounts for the real process phenomena, including the capacity control of screw compressors and variations in the heat-transfer coefficients of an evaporator and a condenser at part load. It also contains an algorithm to determine how the condenser fans are staged in response to a set-point condensing temperature. The model parameters are identified, based on the performance data of chiller specifications. The chiller model is validated using a wide range of operating data of an air-cooled screw chiller. The difference between the measured and modelled COPs is within ±10% for 86% of the data points. The chiller's COP can increase by up to 115% when the set-point condensing temperature is adjusted, based on any given outdoor temperature. Having identified the variation in the chiller's COP, a suitable strategy is proposed for air-cooled screw chillers to operate at maximum efficiency as much as possible when they have to satisfy a building's cooling-load.
机译:本文提出了一种热力学模型来评估风冷螺杆制冷机在各种工况下的性能系数(COP)。该模型考虑了实际的过程现象,包括螺杆压缩机的容量控制以及部分负荷下蒸发器和冷凝器的传热系数变化。它还包含一种算法,用于确定冷凝器风扇如何响应设定点冷凝温度进行分级。基于冷却器规格的性能数据来识别模型参数。该冷水机模型使用了风冷螺杆冷水机的广泛运行数据进行了验证。对于86%的数据点,实测COP和建模COP之间的差异在±10%以内。根据任何给定的室外温度调节设定的冷凝温度,冷水机组的COP最高可增加115%。在确定了冷水机组COP的变化后,提出了一种合适的策略,使风冷螺杆冷水机组在必须满足建筑物的冷负荷时能够以最大的效率运行。

著录项

  • 作者

    Chan KT; Yu FW;

  • 作者单位
  • 年度 2006
  • 总页数
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号