首页> 外文OA文献 >Induced voltages and power losses in single-conductor armored cables
【2h】

Induced voltages and power losses in single-conductor armored cables

机译:单芯铠装电缆中的感应电压和功率损耗

摘要

Single-conductor armored cables are often used to carry high currents in buildings. This paper presented an experimental investigation into both induced voltages and cable resistances associated with the installation of these cables within the buildings. Both induced armor voltages and cables resistances under different installation practices were measured at both power frequency and its harmonic frequencies. The impact of cable formation, bonding arrangement and cable supporting method on these issues were addressed, and illustrated experimentally via 185 mm2 (365 kcmil) single-conductor armored copper stranded cables. The standing voltage is generally small for the armored cables used in the buildings. Power losses increase significantly when the cable armor is bonded at two cable ends, especially in the case of rich harmonic currents in the cables. Recommendations are finally provided for the installation of single-conductor armored cables in buildings.
机译:单芯铠装电缆通常用于在建筑物中承载大电流。本文对与在建筑物内安装这些电缆相关的感应电压和电缆电阻进行了实验研究。在不同的安装方式下,在电源频率及其谐波频率下测量了铠装感应电压和电缆电阻。讨论了电缆形成,键合布置和电缆支撑方法对这些问题的影响,并通过185 mm2(365 kcmil)单芯铠装铜绞线通过实验进行了说明。对于建筑物中使用的铠装电缆而言,常压通常很小。当电缆铠装在电缆的两个端部粘合时,功率损耗会显着增加,尤其是在电缆中存在大量谐波电流的情况下。最后提供了在建筑物中安装单芯铠装电缆的建议。