首页> 外文OA文献 >Electrical and thermal analysis of parallel single-Conductor cable installations
【2h】

Electrical and thermal analysis of parallel single-Conductor cable installations

机译:平行单导体电缆安装的电气和热分析

摘要

The unequal current distribution in parallel single-conductor cable installations can lead to an excessive temperature rise. This paper presented a cable model and a procedure of coupled electrical and thermal analysis for the evaluation of currents, losses and temperatures in the cables of concern. The cable model and analytic method were validated experimentally in the laboratory. The procedure was applied to evaluate the current rating, the temperature rise in a particular single-conductor installation. It is concluded that the parallel cable installation without proper cable rephrasing de-rates the cables significantly. The 3rd order harmonic current can cause a significant reduction of the current rating if its distortion is over 30%.
机译:并联单芯电缆安装中的电流分布不均会导致温度过度升高。本文介绍了电缆模型以及耦合的电气和热分析程序,以评估所关注电缆中的电流,损耗和温度。电缆模型和分析方法在实验室进行了实验验证。该程序用于评估额定电流,特定单导体安装中的温度升高。结论是,没有适当改写电缆的并行电缆安装会严重降低电缆的额度。如果三阶谐波电流的失真超过30%,则可能导致电流额定值的显着降低。