Analyses of operations of control valves in air-conditioning systems comprising multiple chillers and chilled water pumps

机译:包含多台冷水机和冷水泵的空调系统中控制阀的运行分析

摘要

In an earlier paper, the guidelines given in the literature on the selection of chilled water flow control valves for air-handling equipment were reviewed and the proper way of selecting this type of control valves was presented. Complementary to that paper, this paper attempts to answer some questions related to the selection and operation of control valves in air-conditioning systems comprising multiple chillers and chilled water pumps. Explanations are given on the limits imposed on the cooling outputs of air-handling units when they are equipped with three-way control valves and are fed with chilled water from a central plant comprising multiple chillers and pumps while some of the chillers and pumps have been shutdown under part-load conditions. The Interactions between the control valves and the chilled water pumps, as they are cycled on and off, in a single-loop and a two-loop pumping system are analysed. The conclusions Include that the differential pressure bypass control valve in a single-loop pumping system should be sized for a flow handling capacity significantly greater than the flow rate of one chiller. For minimising the disturbances to the temperature control function of air-conditioning systems, control valves with linear Inherent characteristics should be used for differential pressure bypass control. Furthermore, for a two-loop pumping system, both the chiller on and off settings for a conventional de-coupler bypass control system should be based on surplus flow rates, and the on/off control over the secondary-loop pumps should avoid requiring each pump to handle a flow rate significantly greater than its rated flow rate.
机译:在较早的论文中,对文献中给出的有关选择用于空气处理设备的冷却水流量控制阀的指南进行了回顾,并提出了选择这种类型的控制阀的正确方法。作为该论文的补充,本文试图回答与包括多个冷却器和冷冻水泵的空调系统中控制阀的选择和操作有关的一些问题。给出了对空气处理单元配备三通控制阀并从包括多个冷却器和泵的中央设备中馈送冷却水的空气处理单元的冷却输出的限制的解释,其中一些冷却器和泵已经安装了。在部分负载条件下关闭。分析了在单回路和两回路抽水系统中,控制阀和冷冻水泵在开闭之间的相互作用。结论包括:单回路泵送系统中的差压旁通控制阀的尺寸应设计成其流量处理能力明显大于一个冷却器的流量。为了将对空调系统温度控制功能的干扰降到最低,应使用具有线性固有特性的控制阀进行差压旁通控制。此外,对于双回路泵送系统,常规去耦器旁路控制系统的冷却器开/关设置均应基于剩余流量,并且对次级回路泵的开/关控制应避免要求每个泵处理的流量明显大于其额定流量。

著录项

  • 作者

    Yik FWH;

  • 作者单位
  • 年度 2001
  • 总页数
  • 原文格式 PDF
  • 正文语种 eng
  • 中图分类

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号