首页> 外文OA文献 >Analisis Pengaruh Pembebanan terhadap Kekuatan Dielektrik Minyak Isolasi Transformator 6,6 KV/380 V di PT.INTIBENUA PERKASATAMA Dumai
【2h】

Analisis Pengaruh Pembebanan terhadap Kekuatan Dielektrik Minyak Isolasi Transformator 6,6 KV/380 V di PT.INTIBENUA PERKASATAMA Dumai

机译:PT。INTIBENUA PERKASATAMA Dumai负载对6.6 KV / 380 V变压器油绝缘的介电强度的影响分析

摘要

The increment of electric energy comsumption causes the transformer to experience a high load and needs to be detected and treated to increase reability and reduce failure. Dielectric strength is one of detection parameter used. The purpose of this research is to analyze dielectric strength of Shell Diala S4 ZX-1 insulating oil based on changes of transformer loading. In this research, breakdown voltage is tested to see the effect of temperature rise due to changes in transformer loadon transformer oil dielectric strength. The relationship between dielectric strength, temperature rise and transformer loading is analyze using correlation and linier regression analyze. The research result strong and positive correlation (r = +0,99) between temperature rise and transformer loading, strong and negative correlation between temperature rise and dielectric strength (r = -0,98), and strong and negative correlation (r = -0,94) between transformer loading and dielectric strength.
机译:电能消耗的增加导致变压器承受高负载,需要对其进行检测和处理以提高可靠性并减少故障。介电强度是使用的检测参数之一。这项研究的目的是根据变压器负载的变化来分析壳牌Diala S4 ZX-1绝缘油的介电强度。在这项研究中,对击穿电压进行了测试,以观察由于变压器负载变化而引起的温度升高对变压器油介电强度的影响。使用相关和线性回归分析来分析介电强度,温升和变压器负载之间的关系。研究结果表明,温度升高与变压器负载之间呈正相关(r = +0,99),温度升高与介电强度之间呈正相关(r = -0,98),正相关与负相关(r =- 0,94)在变压器负载和介电强度之间。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号