首页> 外文OA文献 >Experimental Investigation on Evaporation Heat Transfer and Pressure Drop Characteristics of HFC-161 in a Horizontal Smooth Tube
【2h】

Experimental Investigation on Evaporation Heat Transfer and Pressure Drop Characteristics of HFC-161 in a Horizontal Smooth Tube

机译:HFC-161在水平光滑管中的蒸发传热和压降特性的实验研究

摘要

The evaporation heat transfer and pressure drop characteristics of HFC-161 in a horizontal smooth tube with an inside diameter of 9 mm was experimentally investigated. The local heat transfer coefficient and total pressure drop were measured at the heat flux ranging from 15 – 25 kW/m2, the mass flux ranging from 100 – 200 kg/(m2·s), and the evaporation temperature of 5, 10 ℃. The experimental results showed that the evaporation heat transfer coefficient increased with the vapor quality except in the high vapor quality region, increased with the mass flux and the heat flux, and decreased with the saturation temperature across the experimental conditions. By comparison, the measured heat transfer coefficient of HFC-161 is higher than that of R22. In addition, the measured total pressure drop of two-phase HFC-161 in the test tube increased strongly with the mass flux within the experimental range. The presented results are helpful in designing more compact and effective heat transfer exchangers for the air-conditioning systems using HFC-161.
机译:实验研究了内径为9 mm的水平光滑管中HFC-161的蒸发传热和压降特性。在15 – 25 kW / m2的热通量,100 – 200 kg /(m2·s)的质量通量和5、10℃的蒸发温度下测量局部传热系数和总压降。实验结果表明,在整个实验条件下,除高蒸气质量区域外,蒸发传热系数均随蒸气质量的增加而增加,随质量通量和热通量的增加而增加,随饱和温度的降低而减小。相比之下,HFC-161的实测传热系数高于R22。另外,随着质量通量在实验范围内,测得的试管中两相HFC-161的总压降大大增加。提出的结果有助于为使用HFC-161的空调系统设计更紧凑,更有效的换热器。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号