System level tests of transformer differential protection using an IEC 61850 process bus

机译:使用IEC 61850过程总线的变压器差动保护的系统级测试

代理获取
本网站仅为用户提供外文OA文献查询和代理获取服务,本网站没有原文。下单后我们将采用程序或人工为您竭诚获取高质量的原文,但由于OA文献来源多样且变更频繁,仍可能出现获取不到、文献不完整或与标题不符等情况,如果获取不到我们将提供退款服务。请知悉。

摘要

The IEC 61850 family of standards for substation communication systems were released in the early 2000s, and include IEC 61850-8-1 and IEC 61850-9-2 that enable Ethernet to be used for process-level connections between transmission substation switchyards and control rooms. This paper presents an investigation of process bus protection performance, as the in-service behavior of multi-function process buses is largely unknown. An experimental approach was adopted that used a Real Time Digital Simulator and 'live' substation automation devices. The effect of sampling synchronization error and network traffic on transformer differential protection performance was assessed and compared to conventional hard-wired connections. Ethernet was used for all sampled value measurements, circuit breaker tripping, transformer tap-changer position reports and Precision Time Protocol synchronization of sampled value merging unit sampling. Test results showed that the protection relay under investigation operated correctly with process bus network traffic approaching 100% capacity. The protection system was not adversely affected by synchronizing errors significantly larger than the standards permit, suggesting these requirements may be overly conservative. This 'closed loop' approach, using substation automation hardware, validated the operation of protection relays under extreme conditions. Digital connections using a single shared Ethernet network outperformed conventional hard-wired solutions.
机译:用于变电站通信系统的IEC 61850系列标准在2000年代初发布,其中包括IEC 61850-8-1和IEC 61850-9-2,这些标准使以太网能够用于传输变电站开关站和控制室之间的过程级连接。 。本文对过程总线保护性能进行了研究,因为多功能过程总线的使用行为在很大程度上是未知的。采用了一种实验方法,该方法使用了实时数字模拟器和“实时”变电站自动化设备。评估了采样同步误差和网络流量对变压器差动保护性能的影响,并将其与传统的硬接线连接进行了比较。以太网用于所有采样值测量,断路器跳闸,变压器分接开关位置报告以及采样值合并单元采样的精确时间协议同步。测试结果表明,所调查的保护继电器在过程总线网络流量接近100%容量的情况下正常运行。保护系统没有受到明显大于标准允许的同步误差的不利影响,这表明这些要求可能过于保守。使用变电站自动化硬件的这种“闭环”方法验证了保护继电器在极端条件下的运行。使用单个共享以太网网络的数字连接优于传统的硬连线解决方案。

著录项

相似文献

  • 外文文献
  • 中文文献
  • 专利
代理获取

客服邮箱:kefu@zhangqiaokeyan.com

京公网安备:11010802029741号 ICP备案号:京ICP备15016152号-6 六维联合信息科技 (北京) 有限公司©版权所有
  • 客服微信

  • 服务号